When the panel shows that the oil temperature has reached the set value, that only means the temperature has been dealt with. It does not mean the oil can leave the tank. A common sequence on site is to open the outlet valve as soon as the temperature is there, and then the first few drums that come out have a water content no better than before the treatment.
The reason is that degassing is a process that takes time, and the temperature control governs only one part of it.
Three times that are not the same
The first is the warm-up time. The oil goes from the ambient temperature up to the set value, and this time is decided by the heating power and the quantity of oil in the tank: the more oil there is and the lower the starting temperature, the slower the rise. The second is the holding time. Once the set value is reached, the temperature has to be held so that the whole tank reaches it. The third is the residence time in the degassing stage, during which the oil circulates and is atomised so that the water and the gas are carried off.
The temperature control system is responsible for the second one, and what it holds is the temperature at the measuring point, not the temperature of the whole tank. The oil at the nozzle, at the bottom of the tank and near the tank wall are not all at the same temperature, and the oil close to the heater is hotter than the oil at the bottom; that difference changes with the flow rate and with the state of the heating.
The temperature is there, the atomisation is not necessarily
How well the degassing works depends on whether the oil is really broken into a fine mist, and the atomisation depends on the viscosity, which in turn changes with the temperature. When the temperature display is at the set value but the flow rate is low, the state of the oil at the nozzle does not fully match the displayed value, and the load on the degassing stage falls short of the design state.
The TYA series makes the temperature control a continuous range of 45–80 °C precisely to leave room for that adjustment: oil with a high viscosity can be run at a higher temperature, and oil with a lot of water can have the upper limit pressed down to 70 °C. Both directions have room in them.

| Stage | What it depends on | What can be seen on site |
|---|---|---|
| Warm-up | The heating power and the quantity of oil | The temperature display keeps rising and has not settled |
| Holding | The regulation of the heating and the temperature control | The temperature is stable around the set value |
| Residence in the vacuum stage | The circulation flow and the working state of the vacuum stage | The vacuum level is stable and the outlet flow is stable |
| Confirmation | Sampling and testing | The water content is judged by GB/T 7600 |
How to judge that the oil can be let out
Before the oil is let out, at least three readings have to be looked at together: the vacuum level stable above -0.08 MPa (the working vacuum of the TYA series is -0.08 MPa), a stable outlet flow, and a temperature that is no longer rising at the set value. Only when all three hold has the machine entered the working state of the degassing stage.
- Letting the oil out as soon as the temperature reaches the set value: what comes out is mixed with oil that has not yet been through the vacuum stage, so the first drums are collected separately.
- Letting the oil out while the vacuum is still unsettled: the degassing stage is not working in a stable state, and there is no guarantee of the figures in the oil that comes out.
- Continuous running and intermittent running are different: in continuous running the oil stays in the circulation, while in intermittent running every round goes through the warm-up and the residence again.
What that time is worth is the test result
Whether the degassing actually got there is decided by the test. A water content of ≤3 ppm (GB/T 7600), a gas content of ≤0.01% (GB/T 423), a breakdown voltage of ≥65 kV (GB/T 507) and cleanliness of NAS class 5 (NAS 1638) are results from a sampled test, not readings on the panel.
The basis for letting the oil out is therefore that the readings are steady and the test has passed; the two together close the round. Letting the oil out on the temperature alone is treating an intermediate step as the result.
The temperature display at the set value only means the heat has reached the tank; whether the oil has really been degassed is answered by the residence time and by the test result.